LG C Series Manual de usuario Pagina 60

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 127
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 59
Chapter 9. Basic functions
CHAPTER 9 - Basic Functions
9.1 Frequency mode
z Digital Frequency setting via Keypad 1
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency Command] - 0/400 0.0 Hz
Drive
group
Frq [Frequency mode] 0
0/8 0
Run frequency is settable in 0.0 - [Frequency Command].
Set Frq – [Frequency mode] to 0 {Frequency setting via Keypad 1}.
Set the desired frequency in 0.0 and press the Prog/Ent (z) key to enter the value into memory.
The value is settable not greater than F21 – [Max frequency].
z Digital Frequency setting via Keypad 2
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency Command] - 0/400 0.0 Hz
Drive
group
Frq [Frequency mode] 1
0/8 0
Run frequency is settable in 0.0 - [Frequency Command].
Set Frq – [Frequency mode] to 1{Frequency setting via Keypad 2}.
In 0.0, frequency is changed upon pressing the Up (S)/Down (T) key. It is selected to use the
Up/Down key as potentiometer on keypad.
The value is settable not greater than F21 – [Max frequency].
60
Vista de pagina 59
1 2 ... 55 56 57 58 59 60 61 62 63 64 65 ... 126 127

Comentarios a estos manuales

Sin comentarios