Total pipe length = A+B+C+D+a+b+c+d+e ≤ 300m(984ft)
L
Longest pipe length Equivalent pipe length(*)
A+B+C+D+e ≤ 150m(492ft) A+B+C+D+e ≤ 175m(574ft)
l
Longest pipe length after 1st branch
B+C+D+e ≤ 40m(131ft)
H
Difference in height (Outdoor Unit ÷ Indoor Unit)
H ≤ 50m(164ft)(40m(131ft) : Outdoor Unit is lower than Indoor Units)
h
Difference in height (Indoor Unit ÷ Indoor Unit)
h ≤ 15m(49ft)
• * : Assume equivalent pipe length of Y branch to be 0.5m(1.6ft),
that of header to be 1m(3,3ft), calculation purpose
Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor
Unit total capacity
[kW(Btu/h)]
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
≤ 22.4(76,400)
Ø9.52(3/8) Ø19.05(3/4)
< 36.4(124,200) Ø9.52(3/8) Ø22.2(7/8)
WARNING
When the any one (or both ) of below conditions are satisfied, the
diameter of main pipe (A) must be increased according to below
table.
- The equivalent length between outdoor unit and the farthest in-
door unit is 90m or more
(Liquid and Gas pipes are increased)
- The level difference (Outdoor unit ÷ Indoor unit) is 50m or more
(Only liquid pipe is increased)
!
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity (HP)
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
4 Ø9.52(3/8) Ø15.88(5/8)
5 Ø9.52(3/8) Ø15.88(5/8)
6 Ø9.52(3/8) Ø19.05(3/4)
Piping parts
Name
① Main pipe
② Branching pipe
③ Indoor unit connecting pipe
Selection
of
pipe size
Outdoor unit
capacity[HP]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
4
Ø9.52(3/8) Ø15.88(5/8)
5
Ø9.52(3/8) Ø15.88(5/8)
6
Ø9.52(3/8) Ø19.05(3/4)
① Size of main pipe
② Pipe size of between branching sections
③ Connecting pipe size of indoor unit
Indoor unit capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8) Ø15.88(5/8)
< 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
< 36.4(124,200) Ø9.52(3/8) Ø22.2(7/8)
Indoor unit capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8) Ø15.88(5/8)
≤ 22.4(76,400)
Ø9.52(3/8) Ø19.05(3/4)
≤ 28.0(95,900)
Ø9.52(3/8) Ø22.2(7/8)
① Outdoor unit ’ 1st branching section
② Branching section
’ Branching section
③ Branching section
’ Indoor unit