Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal
block.
Round pressure terminal
Power cable
- For wiring, use the designated power cable and connect firmly, then
secure to prevent outside pressure being exerted on the terminal
block.
- Use an appropriate screwdriver for tightening the terinal screws. A
screwdriver with a small head will strip the head and make proper
tighterning impossible.
- Over-tightening the terminal screws may break them.
CAUTION
• Use the 2-core shield cables for communication cables. Never use
them together with power cables.
• The conductive shielding layer of cable should be grounded to the
metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading
capacitor not only will deteriorate power factor improvement effect,
but also may cause capacitor abnormal heating. Therefore, never in-
stall a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2%.
If it is greater the units lifespan will be reduced.
!
Side panel
WARNING
The temperature sensor for outdoor air should not be exposed to
direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
!
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal
block. (Slack in the power wiring may cause abnormal heat.)
- When connecting cable which is the same thickness, do as shown in
the figure below.
Pictures may differ depending on the model.
4HP/5HP/6HP
Indoor communication PCB
Main PCB
Terminal block
(Take care of the phase
sequence of 3-phase
4-wire power system)
PI485 PCB
(Inside the control box)
(Inside the control box)
Control box and connecting position of wiring
- Remove all of the screws at side panel and remove the panel by
pulling it forward.
- Connect communication cables between outdoor unit and indoor
units through the terminal block.
- When the central control system is connected to the outdoor unit, a
dedicated PCB must be connected between them.
- When connecting communication cable between outdoor unit and in-
door units with shielded cable, connect the shield ground to the earth
screw.