System Set-Up
ENGLISH
Hydro Kit Installation Manual 41
• Function Code 26 and 27 : Setting Disinfection operation
Disinfection operation is special Domestic Hot Water tank operation mode to kill and to prevent
growth of viruses inside the tank.
- Value #1 of Function Code 26 : Selecting disinfection operation mode. ‘00’ for setting disinfection
mode off, and ‘01’ for setting disinfection mode on.
- Value #2 of Function Code 26 : Determining the date when the disinfection mode is running. ’01’
for Sunday, ’02’ for Monday, … , and ’06’ for Saturday.
- Value #3 of Function Code 26 : Determining the time when the disinfection mode is running. ’00’
for 0:00am, ’01’ for 01:00am, … , ’22’ for 10:00pm, and ’23’ for 11:00pm.
- Value #1 of Function Code 27 : Target temperature of disinfection mode.
- Value #2 of Function Code 27 : Duration of disinfection mode.
WARNING
Vales of Function Code 26
• If Value #1 of Function Code 26 is set as ’00’, Value #2 and Value #3 is not used.
• When Value #1 is set as ’01’, Value #2 is displayed at the position of Value #1 and Value #3 is
displayed at the position of Value #2 due to limited width of the control panel display.
CAUTION
Domestic Hot Water heating should be enabled
• If Domestic Hot Water heating is disabled, the disinfection
mode will not be operated although Value #1 of Code 26
is set as ’01’.
• To use disinfection mode, Domestic Hot Water heating
should be enabled.
Press repeatedly Button to enable
Domestic Hot Water tank heating
<Domestic Hot Water Heating Disable>
<Domestic Hot Water Heating enable>